Wire Size for 40 Amps

A 40-amp load at 240 V over a 100 ft run needs 8 AWG copper (50 A rating · 6.11 V drop (2.5%)). Change the distance or voltage to re-size.

Wire Size for 40 Amps

Minimum wire size8 AWG50 A rating · 6.11 V drop (2.5%)
Copper THHN/THWN at 75 °C — voltage drop for this run
SizeAmpacityVoltage drop
14 AWG20 A24.56 V (10.2%)
12 AWG25 A15.44 V (6.4%)
10 AWG35 A9.68 V (4%)
8 AWG50 A6.11 V (2.5%)
6 AWG65 A3.93 V (1.6%)
4 AWG85 A2.46 V (1%)
3 AWG100 A1.96 V (0.8%)
2 AWG115 A1.55 V (0.6%)
1 AWG130 A1.23 V (0.5%)
1/0 AWG150 A0.98 V (0.4%)
2/0 AWG175 A0.77 V (0.3%)
3/0 AWG200 A0.61 V (0.3%)
4/0 AWG230 A0.49 V (0.2%)
250 kcmil255 A0.41 V (0.2%)
300 kcmil285 A0.34 V (0.1%)
350 kcmil310 A0.29 V (0.1%)
500 kcmil380 A0.21 V (0.1%)

NEC Table 310.16 (75 °C column), 240.4(D) small-conductor limits and Chapter 9 Table 8 resistance. Apply continuous-load (125%), ambient temperature and bundling corrections, and follow your local code and AHJ.

Planning estimates only. Building codes, loads and material specs vary — have a licensed engineer or contractor confirm quantities and safety requirements. Disclaimer

Free Wire Size for 40 Amps by pGento

Frequently asked questions

Is my data uploaded?
No. The calculation runs entirely in your browser — nothing you type is sent to a server.
Is it free?
Yes — free, unlimited and no sign-up.
Wire Size for 40 Amps

Embed this tool on your site

Paste this code into any web page. It stays free, fast and ad-free inside your site.

Print or save as PDF

Prints just this tool and its result. Choose “Save as PDF” as the printer to get a file. Branding is stored only in this browser.