Wire Size for 60 Amps
A 60-amp load at 240 V over a 100 ft run needs 6 AWG copper (65 A rating · 5.89 V drop (2.5%)). Change the distance or voltage to re-size.
Wire Size for 60 Amps
Minimum wire size65 A rating · 5.89 V drop (2.5%)
| Size | Ampacity | Voltage drop |
|---|---|---|
| 14 AWG | 20 A | 36.84 V (15.4%) |
| 12 AWG | 25 A | 23.16 V (9.7%) |
| 10 AWG | 35 A | 14.52 V (6%) |
| 8 AWG | 50 A | 9.17 V (3.8%) |
| 6 AWG | 65 A | 5.89 V (2.5%) |
| 4 AWG | 85 A | 3.7 V (1.5%) |
| 3 AWG | 100 A | 2.94 V (1.2%) |
| 2 AWG | 115 A | 2.33 V (1%) |
| 1 AWG | 130 A | 1.85 V (0.8%) |
| 1/0 AWG | 150 A | 1.46 V (0.6%) |
| 2/0 AWG | 175 A | 1.16 V (0.5%) |
| 3/0 AWG | 200 A | 0.92 V (0.4%) |
| 4/0 AWG | 230 A | 0.73 V (0.3%) |
| 250 kcmil | 255 A | 0.62 V (0.3%) |
| 300 kcmil | 285 A | 0.51 V (0.2%) |
| 350 kcmil | 310 A | 0.44 V (0.2%) |
| 500 kcmil | 380 A | 0.31 V (0.1%) |
NEC Table 310.16 (75 °C column), 240.4(D) small-conductor limits and Chapter 9 Table 8 resistance. Apply continuous-load (125%), ambient temperature and bundling corrections, and follow your local code and AHJ.