Wire Size for 175 Amps
A 175-amp load at 240 V over a 100 ft run needs 2/0 AWG copper (175 A rating · 3.38 V drop (1.4%)). Change the distance or voltage to re-size.
Wire Size for 175 Amps
Minimum wire size175 A rating · 3.38 V drop (1.4%)
| Size | Ampacity | Voltage drop |
|---|---|---|
| 14 AWG | 20 A | 107.45 V (44.8%) |
| 12 AWG | 25 A | 67.55 V (28.1%) |
| 10 AWG | 35 A | 42.35 V (17.6%) |
| 8 AWG | 50 A | 26.74 V (11.1%) |
| 6 AWG | 65 A | 17.18 V (7.2%) |
| 4 AWG | 85 A | 10.78 V (4.5%) |
| 3 AWG | 100 A | 8.57 V (3.6%) |
| 2 AWG | 115 A | 6.79 V (2.8%) |
| 1 AWG | 130 A | 5.39 V (2.2%) |
| 1/0 AWG | 150 A | 4.27 V (1.8%) |
| 2/0 AWG | 175 A | 3.38 V (1.4%) |
| 3/0 AWG | 200 A | 2.68 V (1.1%) |
| 4/0 AWG | 230 A | 2.13 V (0.9%) |
| 250 kcmil | 255 A | 1.8 V (0.8%) |
| 300 kcmil | 285 A | 1.5 V (0.6%) |
| 350 kcmil | 310 A | 1.28 V (0.5%) |
| 500 kcmil | 380 A | 0.9 V (0.4%) |
NEC Table 310.16 (75 °C column), 240.4(D) small-conductor limits and Chapter 9 Table 8 resistance. Apply continuous-load (125%), ambient temperature and bundling corrections, and follow your local code and AHJ.
Planning estimates only. Building codes, loads and material specs vary — have a licensed engineer or contractor confirm quantities and safety requirements. Disclaimer