Wire Size for 80 Amps
A 80-amp load at 240 V over a 100 ft run needs 4 AWG copper (85 A rating · 4.93 V drop (2.1%)). Change the distance or voltage to re-size.
Wire Size for 80 Amps
Minimum wire size85 A rating · 4.93 V drop (2.1%)
| Size | Ampacity | Voltage drop |
|---|---|---|
| 14 AWG | 20 A | 49.12 V (20.5%) |
| 12 AWG | 25 A | 30.88 V (12.9%) |
| 10 AWG | 35 A | 19.36 V (8.1%) |
| 8 AWG | 50 A | 12.22 V (5.1%) |
| 6 AWG | 65 A | 7.86 V (3.3%) |
| 4 AWG | 85 A | 4.93 V (2.1%) |
| 3 AWG | 100 A | 3.92 V (1.6%) |
| 2 AWG | 115 A | 3.1 V (1.3%) |
| 1 AWG | 130 A | 2.46 V (1%) |
| 1/0 AWG | 150 A | 1.95 V (0.8%) |
| 2/0 AWG | 175 A | 1.55 V (0.6%) |
| 3/0 AWG | 200 A | 1.23 V (0.5%) |
| 4/0 AWG | 230 A | 0.97 V (0.4%) |
| 250 kcmil | 255 A | 0.82 V (0.3%) |
| 300 kcmil | 285 A | 0.69 V (0.3%) |
| 350 kcmil | 310 A | 0.59 V (0.2%) |
| 500 kcmil | 380 A | 0.41 V (0.2%) |
NEC Table 310.16 (75 °C column), 240.4(D) small-conductor limits and Chapter 9 Table 8 resistance. Apply continuous-load (125%), ambient temperature and bundling corrections, and follow your local code and AHJ.
Planning estimates only. Building codes, loads and material specs vary — have a licensed engineer or contractor confirm quantities and safety requirements. Disclaimer